Eaton Electrical Powerware 9315 Power Supply User Manual


 
Using the Monitor Panel
5-3
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
You can use the LCD screen and the buttons beneath it to:
Ī Monitor UPS operation
Ī Look at a log of UPS e vents (alarms, notices, and commands)
5.2 Using the Buttons
The buttons below the LCD screen are labeled with arrows indicating their functions:
Ī Press the and buttons to move through the options in a menu, or to scroll through
thelistofalarmsandnoticesintheeventlog.
Ī Press the and buttons to move through the menu titles on the menu bar. Press
them simultaneously to silence the horn, or to test the lamps behind the status
indicators.
Ī Press the button to toggle the use of the and buttons between the menu box
and the information area.
5.3 Adjusting the Contrast
Use the buttons to adjust the contrast on the LCD screen. Hold down the button, then
press the
button to increase the contrast or the button to decrease the contrast.
5.4 Using the Load Off Button
The LOAD OFF button is red and covered by a clear plastic shield. In an emergency, you
can press this button to cut off utility power to the power processing unit of the UPS and
to the critical load. For more information, see Chapter 11, “Using the LOAD OFF Button.”
CAUTION
All power to the critical load is lost when you press the LOAD OFF button. You should use the
LOAD OFF button only when you want to de-energize the critical load.