Communication
7-11
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
7.6.3 Meters Printout – [Ctrl]+[M]
This key sequence prints the current readings of the UPS system meters. The input area
shows the phase-to-phase voltage, frequency, and phase current of the incoming utility,
followed by the kVA, kW, and power factor measurements. The output area shows the
same information for the power being output by the UPS. The Bypass area shows the
phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V)
and the DC current (I). Figure 7-7 shows a sample Meters printout.
Input Output
Bypass Battery
VAB
480
VBC VCA
KW
379
KVA
399
IA IB IC
FREQ
60.0
PF
0.95
V
540
I
0
480
480 480
480480
VAB
480
VBC VCA
480 480
IA IB IC
361 361361
IN
0
VAB
480
VBC VCA
480 480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
03 JAN 1997 14:22:49
+
Figure 7-7. System Meters