Eaton Electrical Powerware 9315 Power Supply User Manual


 
Communication
7-7
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
Table 7-3 shows which optionsareavailableforeachport.Thesectionsthatfollow
describe the configuration settings you can change.
Table 7-3. Available Options for Each Communication Port
Port 1 Port 2 Options
X X Terminal Mode
X Calibration Mode
X X System Configuration Mode
X Computer Mode
X Remote Monitor Mode
X X Baud rate of 300, 1200, 2400, 4800, 9600, or 19200
X X Data size/stop bits of 8/1 or 8/2
X Data size/stop bits of 7/1 or 7/2
X X Disabled handshaking
X X XON/XOFF handshaking
NOTE You should change Port 2 options only if field service has performed a wiring change.
7.5.1 Mode
The operational mode of the port. Each communication port operates in one of the
following modes:
Terminal Mode
System events are logged immediately as they occur.
System Configuration
Mode
Allows you to set building alarms, battery tests, etc.
(Check with your sales or service representative for availability.)
Calibration Mode
Used only by service personnel.
Computer Mode
Provides a proprietary Binary Computer Mode (BCM) Interface.
Remote Monitor Mode
Sends all system event information to an RMP, RIM, or SCM.
Available for Port 1 only.
Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be
operating in different modes. The modes are described later in this chapter.
7.5.2 Rate
The baud rate of the equipment connected to this port. The baud rate determines the
speed of data transferred between the UPS and the connected equipment. For Remote
Monitor mode, the baud rate must be set to 300. All other modes should operate at the
highest baud rate available with the connected equipment. 300 baud is not recommended
for any mode except Remote Monitor.
You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19200.