Product Specifications
9-2
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
Table 9-3. System Output
Rectifier/Charger Capacity
125%
DC Filtering
Ripple voltage less than 0.5% peak to peak
UPS Output Capacity
100% rated current
Output Voltage Regulation
1% (10% to 100% load)
Output Voltage Adjustment
(Nominal +/–5%)
208 Vac nominal, adjustable from 198 Vac to 218 Vac (60 Hz only)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)
Output Voltage Harmonic Content
3% max THD, 2% max single (linear load)
Output Voltage Balance
3% for 100% maximum load imbalance
Output Voltage Phase
Displacement
3° for 100% maximum load imbalance
Output Transients
5% for 100% load step or removal
Frequency Regulation
0.01 Hz free running
Synchronous to Bypass
Bypass within voltage limits of +5%, –8% of output setting; bypass within
±0.5 Hz
Frequency Slew Rate
1 Hz per second maximum (adjustable)
Overload Capability
125% for 10 minutes
150% for 10 seconds
Maximum Output Capability
300% peak for 10 cycles without bypass
Table 9-4. Environmental Specifications
Operating Temperature
0 to 40°C without derating. However, operating at or near 40°C will
adversely affect battery life (refer to your battery specifications for more
information). The recommended operating temperature is 25°C.
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
–20 to +70°C (prolonged storage above 40°C will cause rapid battery
self-discharge)
Relative Humidity (operating and
storage)
95% maximum noncondensing
Acoustical Noise
65 dBA at a 1m distance
EMI Suppression
Meets FCC Regulation 47, Part 15, Subpart J, for class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and
with no disturbance or adverse effect to the critical load.