Maintaining the UPS System
8-2
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
WARNING
Ī Do not dispose of the battery or batteries in a f ire. Batteries may explode. Proper disposal
of batteries is required. Refer to your local codes for disposal requirements.
Ī Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
CAUTION
Do not discard the UPS or the UPS ba tteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed of properly. For more information, contact your local
recycling or hazardous waste center.
AVERTISSEMENT!
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre les
précautions qui s’imposent.
Ī Pour le remplacement, utiliser le même nombre et modéle des batteries.
Ī L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.
8.2 Performing Preventive Maintenance
The UPS requires very little preventive maintenance. However, the UPS should b e inspected
periodically to verify that it is operating normally and that the batteries are in good
condition.
Perform the following checks DAILY:
Ī Check the area surrounding the UPS. Ensure the area is not cluttered, allowing free
access to the UPS.
Ī Ensuretheairintakes(ventsonthefront doors) and exhaust opening (on top of the
UPS cabinet) are not blocked.
Ī Ensure the operating environment is within the parameters specified in Chapter 9,
“Product Specifications.”
Ī Ensure the UPS is in Normal mode (Normal status indicator is lit). If an alarm lamp is lit
or the Normal status indicator is not lit, contact your Eaton service representative.
Perform the following checks MONTHLY:
Ī Ensure all status indicator lamps are operative. (Press the and buttons
simultaneously to test the lamps.)
Ī Monitor system parameters as described in Chapter 5, “Using the Monitor Panel.”
Ī Check the air filters (located behind the front doors) and replace them as necessary (the
filter size is 16″
×20″×1″).
Ī Recordtheresultsofyourchecksandanycorrectiveactionsinasuitablelog.