Eaton Electrical Powerware 9315 Power Supply User Manual


 
9-1
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
Chapter 9 Product Specifications
The UPS systems are housed in freestanding, double-front cabinets with safety shields
behindthedoors.TheUPSsystemsareavailablein50/60Hzwithvariousoutputpower
ratings. Smaller models within a system may be upgraded in the field to larger models:
Table 9-1. Model Numbers
System Models Notes
Powerware 9315 300 225 and 300 kVA 60 Hz only
Powerware 9315 250 200 and 250 kVA 50/60 Hz (400V models only)
Powerware 9315 225 225 kVA 60 Hz only
Powerware 9315 200 200 kVA 50/60 Hz (400V models only)
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
Table 9-2. System Input
Operating Input
Voltage
(Nominal +10/–15%)
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)
Operating Input
Frequency Range
3Hzofnominal(50Hzor60Hz)
Operating Input
Current
Battery Charge
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge with 0.8 pF
output units
115% of full load for overload + battery charge
Actual load + 15% of full load for battery charge with 0.9 pF
output units
Reduced for Generator
Adjustable, set to 102%
Input Current
Harmonic Content
10% THD at full load (with input filter option installed)
Power Walk-In
Adjustable 3– 60 second rectifier ramp-up to full utility load
Power Factor
Minimum 0.95
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4