Using the Monitor Panel
5-9
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
Select Unit from the Statistics menu to display a listing of statistics about UPS operation.
Figure 5-7 shows the Unit Statistics screen.
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
04 NOV 1997 14:23:45
Events Statistics Graphics SetupMeters
Statistics
Unit
Start Date: 04 MAY 1997
Number of Incidents:
On Battery < 1 Min.
On Battery 1 -4 Min.
On Battery > 4 Min.
Full Batt. Discharge
Building Alarm 1
Building Alarm 2
Building Alarm 3
Building Alarm 4
Building Alarm 5
Building Alarm 6
UPS
Bypass
Battery
Generator
Logic
Availability
UPS
Bypass
0
1
0
0
2
2
3
2
3
3
0
0
0
0
11
9
8
5
8
9
0.99
0.81
100%
Percent
Battery
Month Total DAYS HR MNTime On:
0035 20 59
0000 00 30
0000 00 02
0000 00 00
0035 21 30
Figure 5-7. Unit Statistics Screen
The left column shows the number of UPS incidents for the current month and total from
the start date shown at the top of the screen. The top right column shows the time that
the UPS was on bypass, battery, or generator, and the amount of time the UPS logic has
been functioning since the start date. The lower right column shows the percent of
availability of the UPS and the bypass source.