Eaton Electrical Powerware 9315 Power Supply User Manual


 
Communication
7-9
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
7.6 Terminal Mode
In this mode, system events are continually logged through the serial port to the device
connected to the port. Port 2 operates by default in Terminal mode.
The printed log entries contain a time and date stamp and the alarm text m essage.
Terminal mode uses this format for printing alarm entries:
MMM DD HH:MM:SS.hh KYWD MESSAGE :::: <CR> <LF>
Symbol Description
MMM Month (3 letters)
DD Day (2 digits)
HH Hour (2 digits)
MM Minute (2 digits)
SS Second (2 digits)
hh Hundredths of Second (2 digits)
KYWD MESSAGE Keyword (ALARM, NOTICE, COMMAND, or S TATUS)
:::: System Diagnostic Information
<CR> Carriage Return Character (ASCII 13)
<LF> Line Feed (ASCII 10)
An alarm message is prefixed by the word “CLEAR” whenever an alarm is entered into the
Event History Log with a cleared status.
7.6.1 Printing Selected Information
If a port is operating in Terminal mode and is connected to a computer, you can use key
combinations at any time to print only selected information:
[Ctrl]+[P]
Prints the entire log with a header
[Ctrl]+[M]
Prints the current system meters with a header
[Ctrl]+[A]
Prints all system information
[Ctrl]+[B]
Prints the Battery Test Log
To use a key combination, hold down the Control key and press the letter key.