Communication
7-6
EATON Powerware
®
9315 UPS (200–300 kVA) Operatio n Manual S 164201036 Rev F powerware.com
7.5 Configuring the Serial Ports
You must configure the port for communication using the LCD screen and buttons on the
UPS Monitor Panel.
Select Port 1 from the Setup menu to display one of the Setup Port screens. The screens
for Port 1 and Port 2 are identical, and allow you to specify settings for the two serial
communication ports. Figure 7-5 shows the Setup Serial Port 1 screen.
NOTE
You should configure only Port 1 unless field service has performed a wiring
change for Port 2.
Statistics Graphics Setup
Setup
Port 1
Uninterruptible Power System
UPS System Normal
Alarm: None
Notice: None
03 NOV 1997 14:23:45
EventsMeters
Setup Serial Port 1
Rate
9600
Data/Stop
81
Handshaking
XON / XOFF
Save
NO
Time
Mode
TERMINAL
Port 2
Battery
100%
Percent
Figure 7-5. Setup Serial Port 1 S creen
A small return arrow (
) appears in the upper right corner of the Setup Port screen. This
arrow is a reminder that you can press the
button on the Monitor Panel to toggle the
buttons between the menu box and the information area.
If the scroll bar is in the menu box, press the
buttontotoggletotheinformation
area. The first setting (Mode) is highlighted. Press the
or button to move the highlight
to the setting you want to change. To scroll through the available options for that setting,
press the
or button.
To save the settings upon exit from this screen, be sure the Save field is set to YES.