Electro-Voice 1252 Computer Monitor User Manual


 
Electro Industries/GaugeTech
Doc # E107706 V1.25 7-5
7.2.1.1:
Three
Element
Loss
Compensation
Worksheet
Q
Transformer Data (from Transformer Manufacturer’s Test Sheet)
Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing
3-Phase values by three. Convert 1-Phase Loss Watts to 1-Phase kW by dividing 1-Phase Loss Watts by
1000.
Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing
3-Phase values by three. Convert 1-Phase Self-Cooled MVA to 1-Phase kVA by multiplying by 1000.
Test Voltage is generally Phase-to-Phase for three-phase transformers. Calculate Phase-to-Neutral
Voltage by dividing Phase-to-Phase Voltage by 3. Calculate Full Load Current by dividing the (1-Phase
kW Self-Cooled Rating) by the (Phase-to-Neutral Voltage) and multiplying by 1000.
Company
Date
Trf Manf
Calculation by
Station Name
Trf Bank No.
Trf Serial No.
ConnectionWinding Voltage MVA
HV - High
- Y
Xv - Low
YV - Tertiary
- Y
- Y
Watts Loss
1-Phase3-Phase 1-Phase kW
Value
No-Load Loss
Load Loss
Value 3-Phase MVA 1-Phase MVA 1-Phase kVA
Self-Cooled Rating
% Exciting Current
% Impedance
Value Phase-to-Phase Phase-to-Neutral
Test Voltage (volts)
Full Load Current (Amps)