Electro-Voice 1252 Computer Monitor User Manual


 
Time
Start/Reset is the time when Flicker was started or reset. A Reset of Flicker causes the Max/Min
values to be cleared and restarts the Flicker Pst and Plt timers. A Start of Flicker is also
equivalent to a Reset in that the PST and PLT are restarted and the Max/Min Values are cleared.
Stop corresponds to the time when Flicker is turned off.
Current is the current clock time.
Next Pst is the countdown time to when the next Pst value is available.
Next Plt is the countdown time to when the next Plt value is available.
Status
Indicates the current status. Active = On. Stopped = Off.
Frequency
Base is the current operating frequency selected by the user (50 or 60 Hz).
Current is the real time frequency measurement of the applied voltage.
Base Voltage is the normalized voltage for the selected frequency (230 V for 50 Hz or 120 V for
60 Hz).
Flicker Monitoring
Clicking on Stop causes Flicker to stop being processed and freezes all the current values. Stop
Time is recorded and clears the current Max/Min Values
Clicking on Start starts Flicker processing. Start Time is recorded.
Clicking on Reset causes the Max/Min values to be cleared and restarts the Flicker Pst and Plt
timers.
Click OK to exit the Flicker screen.
Click Help for more information on this topic.
Q
Instantaneous Readings
Refer to the Instantaneous section of the Main screen above. If you are on the Short or Long Term
screens, click on the Instantaneous tab to display the Instantaneous screen. The PU values, Pinst for
Voltage Inputs Va, Vb and Vc are displayed here and are continuously updated. The corresponding
Current Voltage values for each channel are displayed for reference.
Electro Industries/GaugeTech
Doc # E107706 V1.25 12-5