Emerson 4000 Switch User Manual


 
2 --- 1 1 Settings
Engine Exerciser S ettings
The controller (CP) engine exerciser setting can be displayed and changed from
the keypad. Some settings may require a password (if the controller is set up for
one).
From any of the Status displays, press Enter/Save Settings keytomovetothe
Settings level of menus.
Press the right arrow key to move to Setting Time Delays menu.
Press the right arrow key again to move to Settings Features menu.
Press the right arrow key again to move to Settings General menu.
Press the right arrow key again to move to Settings Engine Exerciser.
Now press Enter/Save Settings keytomovetothefirstEngine Exerciser menu.
You can press the right arrow key to see the other Engine Exerciser menus
(as shown below). An overview explanation of each setting is listed below.
8 Engine Exerciser Settings M enus
(last menu loops back to first)
Present Date/Time seepage21
This display allows the user t o change t he controller date and time.
US DST — US Daylight Saving Time. APR – OCT, MAR – NOV, or OFF.
MAR NOV begins in 2007.
P(1—7) Engine Exerciser(s) seepage21
These displays (P1 through P7) allow the user to set the controller’s seven
independent engine exerciser routines. Each routine functions in the same
manner. Six parameters need to be configured for each routine (P1, P2, P3,
P4, P5, P6, P7 not al l have to be used).
Enable YES e n ables the routine; NO turns it off.
wLoad YES transfers load to Emergency; NO = no transfer.
Start when the routine will start the generator
time (hour, minute)
week (all, alternate, 1st, 2nd, 3rd, 4th, or 5th week)
–dayoftheweek(mon,tue,wed,thu,fri,sat,sun)
Run Time duration (length of time) that the generator will run.
SETTINGS
Voltage DO P U
Frequency DO PU
PR ESENT DAT E/T IME
US DST:
Date:
Time:
P1 ENGINE EX ERCISER
Enable: wLoad:
Start: h
Run Time: h min
SETTINGS
Engine Exerciser
②③
④⑤
P7 ENGINE EX ERCISER
Enable: wLoad:
Start: h
Run Time: h min
Set the se ven
independe nt
engine exercise
routines,
if desired.