2--12Settings
View Event Log
The controller event logging feature can be displayed from the keypad. Some
settings m ay require a password (if the controller is set up for one).
¡ From any of the Status displays, press Enter/Save Settings key to move to
the Settings level of menus.
© Press the right arrow " key to m ove to Setting Time Delays menu.
¢ Press the right arrow " key again to move to Settings Features menu.
£ Press the right arrow " key again to move to Settings General menu.
¤ Press the right arrow " key again to move to Settings Engine Exerciser.
¥ Press the right arrow " key again to move to View Event Log.
¦ Now p ress Enter/Save Settings keytomovetotheeventsloggeddisplay.
§ You can press the right arrow " key to see the other events logged.
An overview explanation of each setting is listed below.
Logged Events
This display shows the last 99 logged events. Each event display shows the
event number (1 is the most recent, 99 is the oldest), the time and date of the
event, the event type, and the event reason (if applicable).
Event Types
Nine types of events are logged. They are (displayed event & meaning) :
Eng Start The controller has signaled the engine to start
Xfer N>E The controller has initiated transfer from normal to emergency
Xfer E>N The controller has initiated transfer from emergency to normal
Eng Stop The controller has signaled the engine to stop
EmergAcc The emergency source has become acceptable
EmergNAccThe emergency source has become not acceptable
NormAcc The normal source has become acceptable
NormNAcc The normal source has become not acceptable
XfrAbort The transfer has been aborted
Event Reasons
Twenty–one reasons for events are logged. They are (displayedreason & meaning):
L oadShed L oad shed requested
NormFail Normal source failure NormOF Normal source over frequency
ManualXfr Manual transfer NormPHR Normal source phase rotation
Test 5 Test requested (Feature 5) NormVUNB Normal source voltage unbalance
Test 17 Test requested (Feature 17) EmergUV Emergency source under voltage
Comm Serial communications EmergOV Emergency source over voltage
EngExerc Engine Ex erciser EmergUF Emergency source under frequency
EmergFail Emerg source failure EmergOF Emergency source over frequency
NormUV Normal source under voltage EmergPHR Emergency source phase rotation
NormOV Normal source over voltage EmergVUNB Emergency source voltage unbalance
NormUF Normal source under frequency Feature 6 Feature 6 activated
SETTINGS
Voltage DO PU
Frequency DO PU
¡
1
No Event Recorded
2
No Event Recorded
VIEW
Event Log
©¢£¤¥
¦
Scroll "
to show the
last 99 logged
events.
§
98
No Event Recorded
99
No Event Recorded