Emerson 4000 Switch User Manual


 
2 --- 6Settings
Features Settings
Unless otherwise specified on the order, the controller features settings are set at the
factory to the default values. If a setting must be changed, follow the procedure on the
next page. Some settings may require a password (if the controller is set up for one).
Any indiscriminate change in these settings may affect the normal operation of the Automatic Trans-
fer Switch. This change could allow the load circuits to remain connected to an inadequate source.
Feature Default Setting Adjustment Range
Display Screen
(see next page)
commit to t ransfer no yes or no
Commit to Xfer After
TD Norm Fail
shed load direction from E from N or from E
SHED LOAD
Direction
shed load in phase no yes or no
SHED LOAD
InPhase
shed load in phase time delay 1.5 second
0to3.0seconds
0.1 sec increments
SHED LOAD
TD
shed load isolate load
on source failure
yes yes or no
SHED LOAD
IsoLoadOnSrcFail
shed load isolate load on test 17
no yes or no
SHED LOAD
IsoLoadOnTest17
phase rotation monitor enable
no yes or no
PHASE ROT ATION
MONITOR
Enable
phase rotation monitor reference
ABC AB C or CBA
PHASE ROT ATION
MONITOR
Reference
inphase monitor enable
no yes or no
IN–PHASE
MONITOR
Enable
inphase monitor time delay
1.5 second
0to3.0seconds
0.1 sec increments
IN–PHASE
MONITOR
Time Delay
failure to sync auto bypass
no yes or no
CTTS BYPASS/SHED LD
FailSyncAutoByps
bypass time delay
0second
0to59seconds
1 sec increments
CTTS BYPASS/SHED LD
Bypass DT Delay
bypass in phase
no yes or no
CTTS BYPASS/SHED LD
Bypass InPhase
Y–Y primary failure detection enable no yes o r no
Y–Y PRI FAIL DETECT
Enable
Y–Y primary failure sensing time delay 1.0 second
0to9.9seconds
0.1 sec increments
Y–Y PRI FAIL DETECT
Sense Delay
Y–Y primary failure retransfer time delay 1.0 hour
0to23hrs59min.
1 min. increments
Y–Y PRI FAIL DETECT
TD E>N Y–Y
These features appear only on the display for a 4ACTS, 7ACTS, or 7ACTB closed–transition transfer switch.
These features appear only on the display for a 4ACTS, 7ACTS or 7ACTB closed–transition transfer switch
or a 4ADTS, 7ADTS, or 7ADTB delayed–transition transfer sw itch.
These features do not appear on the display unless both sources have 3 phase sensing enabled.
These features appear only on a 4ATS, 7ATS, or 7ATB (open–transition automatic transfer switch).