User Instructions UM582127000
Spec. No. 582127000 (Model 721NPBB) Issue AC, January 2, 2013
Chapter 4. Troubleshooting and Repair Page 55
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-17
Replacing a Distribution Panel
Components removed in illustration for clarity only.
Front Front
Battery
Distribution
Panel
Load
Distribution
Panel
Ground Busbar
Hardware
Ground Busbar
Hardware
Battery Busbar
Hardware
Distribution Panel
Hardware
System Load
Distribution Busbar
Hardware
Distribution Panel
Hardware
/+24/ jumpers.
Assembly order is: lug, 1/4" flat washer,
1/4" lock washer, 1/4-20 bolt.
Torque to 84 in-lbs.
List DA Dual Voltage
Distribution Panel
(Lists DB, DC, and DD similar.)