UM582127000 User Instructions
Issue AC, January 2, 2013 Spec. No. 582127000 (Model 721NPBB)
Page 58 Chapter 4. Troubleshooting and Repair
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-19
Replacing a Battery Disconnect Contactor
in a 2, 3, or 4-Row Distribution Cabinet
Battery
Disconnect
Contactor
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Components removed in
illustration for clarity only.
Front
2-row Distribution Cabinet
shown, 3 or 4-row cabinet similar.
Shown being removed from front
for clarity only. Removal is from rear.
1/2-13 x 1-1/4” Bolt
1/2" Belleville Lock Washer
1/2" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
1/2" Hardened Flat Washer
(4 places)
Torque to 500 in-lbs.
White/Black
Wire
Brown Wire
Brown/White Wire
Red/White
Wire