Emerson 721NPBB Power Supply User Manual


 
User Instructions UM582127000
Spec. No. 582127000 (Model 721NPBB) Issue AC, January 2, 2013
Chapter 4. Troubleshooting and Repair Page 59
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-20
Replacing a Load Disconnect Contactor
in a 1-Row Distribution Cabinet
Load
Disconnect
Contactor
Components removed in
illustration for clarity only.
Front
5/16-18 x 1Bolt
5/16" Belleville Lock Washer
5/16" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
5/16" Hardened Flat Washer
(4 places)
Torque to 100 in-lbs.
Apply electrical anti-oxidizing
compound to busbar
mating surfaces.
Contactor styles vary
between manufacturers.
Black Wire
Violet/White Wire
Violet Wire
Red Wire
Violet/White Wire
Violet Wire
Black Wire
Red Wire