GE MM200 Network Router User Manual


 
COMMUNICATIONS GUIDE RS485 INTERFACE (MODBUS RTU)
MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE 13
30272 010F Reserved --- --- --- --- --- --- 1
30273 0110 Restart Block --- --- --- s F1 N/A 1
30274 0111 Reserved --- --- --- --- --- --- 1
▼▼
30282 0119 Reserved --- --- --- --- --- --- 1
CONTACT/VIRTUAL INPUTS/OUTPUTS STATUS
30283 011A Reserved --- --- --- --- --- --- 2
30285 011C Contact Input 7-1 (Bit Field) --- --- --- --- FC167 N/A 2
30287 011E Reserved --- --- --- --- --- --- 1
▼▼
30297 0128 Reserved --- --- --- --- --- --- 1
30298 0129 Contact Output 3-1 (Bit Field) --- --- --- --- FC167 N/A 2
30300 012B Reserved --- --- --- --- --- --- 1
30301 012C Reserved --- --- --- --- --- --- 1
SECURITY
30302 012D Current Security Access Level --- --- --- --- F1 N/A 1
30303 012E Reserved --- --- --- --- --- --- 1
30304 012F Reserved --- --- --- --- --- --- 1
STATUS - MOTOR
30305 0130 Motor Status --- --- --- --- FC129 N/A 1
30306 0131 Extended Status --- --- --- --- FC178 N/A 1
30307 0132 Thermal Cap Used --- --- --- % F1 N/A 1
30308 0133 Time to Overload Trip --- --- --- s F20 N/A 2
30310 0135 Drive Status --- --- --- --- FC143 N/A 1
30311 0136 Reserved --- --- --- --- --- --- 1
30312 0137 Command Status --- --- --- --- FC128 N/A 1
30313 0138 Reserved --- --- --- --- --- --- 1
30314 0139 Reserved --- --- --- --- --- --- 1
▼▼
30327 0146 Reserved 1
CURRENT METERING
30328 0147 Ia --- --- --- A F10 N/A 2
30330 0149 Ib --- --- --- A F10 N/A 2
30332 014B Ic --- --- --- A F10 N/A 2
30334 014D Iavg --- --- --- A F10 N/A 2
30336 014F Motor Load --- --- --- % F1 N/A 1
30337 0150 Current Unbalance --- --- --- %Ub F1 N/A 1
30338 0151 Ig --- --- --- A F10 N/A 2
30340 0153 Reserved --- --- --- --- --- --- 1
▼▼
30434 01B1 Reserved --- --- --- --- --- --- 1
TEMPERATURE METERING
30435 01B2 Thermistor --- --- --- ohms F1 N/A 1
30436 01B3 Reserved --- --- --- --- --- --- 1
▼▼
30466 01D1 Reserved 1
Modbus Hex Description Min Max Step Units Format Default Size in
Words