26 MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU) COMMUNICATIONS GUIDE
FC174 16 bits Source Stop Action
0Stop
1Trip
FC175 16 bits Test Auto/Manual Mode
0ON
1OFF
2 Unaffected
FC178 16 bits Motor Status
Bit 0 Lockout
Bit 1 Non-Lockout Trip
Bit 4 Running
Bit 5 Precontactor
Bit 6 Starting
Bit 8 Inhibit
Bit 9 Stopped
Bit 10 Self Test Fault
Bit 11 Alarm
Bit 12 Forward
Bit 13 Reverse
Bit 14 Low Speed
Bit 15 High Speed
FC179 32 bits Alarm Status 1
Bit 0 Any Alarm
Bit 1 Thermal Level Alarm
Bit 2 Ground Fault Alarm
Bit 3 Acceleration Alarm
Bit 9 UnderCurrent Alarm
Bit 10 Unbalance Alarm
FC180 32 bits Alarm Status 2
Bit 0 Aux U/V Alarm
Bit 1 External Stop Alarm
Bit 3 Open Ctrl Cct Alarm
Bit 4 Thermistor Alarm
Bit 6 External Start A Alarm
Bit 7 External Start B Alarm
Bit 8 Welded Contactor
Bit 12 Load Increase Alarm
Bit 13 Drive Greasing Alarm
Bit 14 Contactor Inspect Alarm
Bit 15 Max Stopped Alarm
Bit 18 Comm Fail Alarm
FC183 32 bits Trip Status 1
Bit 0 Any Trip
Bit 1 Thermal O/L Trip
Bit 2 Ground Fault Trip
Bit 3 Acceleration Trip
Bit 8 Mechanical Jam Trip
Code Type Definition