20 MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU) COMMUNICATIONS GUIDE
Format codes
CONTACT OUTPUTS
41515 05EA Contact Output 1 0 57344 0 --- FC142 0 1
41516 05EB Contact Output 2 0 57344 0 --- FC142 0 1
41517 05EC Contact Output 3 0 57344 0 --- FC142 0 1
41518 05ED Reserved --- --- --- --- --- --- 1
▼▼
41571 0622 Reserved --- --- --- --- --- --- 1
AUTO / MANUAL CONTROL
41572 0623 Comms Start Ctrl 0 1 1 --- FC126 0 1
41573 0624 Comms Stop Mode 0 1 1 --- FC172 0 1
41574 0625 Hard Wired Start Ctrl 0 1 1 --- FC126 0 1
41575 0626 Hard Wired Stop Mode 0 1 1 --- FC172 0 1
41576 0627 Hard Wired Stop Actn 0 1 1 --- FC174 0 1
41577 0628 Hard Wired 2W/3W 0 1 1 --- FC173 1 1
41578 0629 Field Start Ctrl 0 1 1 --- FC126 0 1
41579 062A Field Stop Mode 0 1 1 --- FC172 0 1
41580 062B Field Stop Action 0 1 1 --- FC174 0 1
41581 062C Field 2W/3W 0 1 1 --- FC173 1 1
41582 062D MCC Start Ctrl 0 1 1 --- FC126 0 1
41583 062E MCC Stop Mode 0 1 1 --- FC172 0 1
41584 062F MCC Stop Action 0 1 1 --- FC174 0 1
41585 0630 Test Auto Mode 0 2 1 --- FC175 1 1
41586 0631 Test Manual Mode 0 2 1 --- FC175 0 1
41587 0632 External Stop Action 0 1 1 --- FC174 0 1
41588 0633 Auto/Manual Key 0 1 1 --- FC126 0 1
Modbus Hex Description Min Max Step Units Format Default Size in
Words
Code Type Definition
F1 16 bits UNSIGNED VALUE
Example: 1234 stored as 1234
F2 16 bits UNSIGNED VALUE, 1 DECIMAL PLACE
Example: 123.4 stored as 1234
F3 16 bits UNSIGNED VALUE, 2 DECIMAL PLACES
Example: 12.34 stored as 1234
F9 32 bits UNSIGNED LONG VALUE
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F10 32 bits UNSIGNED LONG VALUE, 1 DECIMAL PLACE
1st 16 bits UNSIGNED LONG VALUE, 1 DECIMAL PLACE
2nd 16 bits Low Order Word of Long Value
Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex