18 MM200 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
RS485 INTERFACE (MODBUS RTU) COMMUNICATIONS GUIDE
ACCELERATION
40851 0352 Acceleration Alarm Timer 5 2501 1 s F2* 2501 1
40852 0353 Acceleration Trip Timer 5 2501 1 s F2* 2501 1
40853 0354 Reserved --- --- --- --- --- --- 1
40854 0355 Reserved --- --- --- --- --- --- 1
40855 0356 Reserved --- --- --- --- --- --- 1
40856 0357 Reserved --- --- --- --- --- --- 1
CURRENT UNBALANCE (REQUIRED=IO_A)
40857 0358 Current Unbalance Alarm Level 4 41 1 % F1* 15 1
40858 0359 Current Unbalance Alarm
Delay
160 1s F11 1
40859 035A Current Unbalance Trip Level 4 41 1 % F1* 30 1
40860 035B Current Unbalance Trip Delay 1 60 1 s F1 1 1
40861 035C Reserved --- --- --- --- --- --- 1
40862 035D Reserved --- --- --- --- --- --- 1
40863 035E Reserved --- --- --- --- --- --- 1
40864 035F Reserved --- --- --- --- --- --- 1
GROUND FAULT
40865 0360 Reserved --- --- --- --- --- --- 1
40866 0361 CBCT Ground Alarm Level 5 151 1 A F2* 151 1
40867 0362 Ground Alarm Delay On Start 0 60 1 s F1 10 1
40868 0363 Reserved --- --- --- --- --- --- 1
40869 0364 CBCT Ground Trip Level 5 151 1 A F2* 151 1
40870 0365 Ground Trip Delay On Start 0 100 1 s F2 0 1
40871 0366 Ground Alarm Delay On Run 0 60 1 s F1 10 1
40872 0367 Ground Trip Delay On Run 0 50 1 s F2 0 1
40873 0368 Reserved --- --- --- --- --- --- 1
40874 0369 Reserved --- --- --- --- --- --- 1
LOAD INCREASE
40875 036A Load Increase Alarm Level 50 151 1 %FLA F1* 151 1
40876 036B Reserved --- --- --- --- --- --- 1
▼▼
40911 038E Reserved --- --- --- --- --- --- 1
MAINTENANCE
40912 038F Drive Greasing Interval 100 50100 100 hrs F1* 50100 1
40913 0390 Contactor Inspection Interval 100 65000 100 ops F1* 65000 1
40914 0391 Max Motor Stopped Time 10 10010 10 hrs F1* 10010 1
40915 0392 Reserved --- --- --- --- --- --- 1
▼▼
41039 040E Reserved 1
CALIBRATION
41040 040F Calibration Date 0 203360302 1 --- F18 0 2
41042 0411 Calibration Time 0 389757795 1 --- F19 0 2
41044 0413 Reserved --- --- --- --- --- --- 1
▼▼
41105 0450 Reserved 1
Modbus Hex Description Min Max Step Units Format Default Size in
Words