Hitachi SJ-PB(T) Power Supply User Manual


 
CHAPTER5 OPERATING
10
This section describes how to control the inverter via control word/status word and how to access the inverters
parameters.
5.1 PPO- description
The structure of the user data is designated as parameter process data objects (PPO) in the Profidrive profile.
The profile defines five PPO types, where SJ-PB supports all these PPO types.
There are PPO’s with a parameter area (PKW) and a process data area (PZD). There is also PPO’s that consist
exclusively of process data (PZD).
1. PPO1 consists of the PKW area and 2 words PZD.
2. PPO2 consists of the PKW area and 6 words PZD.
3. PPO3 consists only of 2 words PZD.
4. PPO4 consists only of 6 words PZD.
5. PPO5 consists of the PKW area and 10 words PZD.
The user can configure what shall be transferred in PZD3-10 (shaded grey below), for more instructions of how to
do this configuration see chapter 5.3.3, 5.4.2, 5.4.3 and Appendix.
PKW PZD
PKE IND PWE PZD1
STW
ZSW
PZD2
HSW
HIW
PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
Word 123456
PPO1
Word 12345678910
PPO2
Word 5 6
PPO3
Word 5678910
PPO4
Word 1234567891011121314
PPO5
PKW -- Parameter ID/value.
PZD -- Process data, cyclically transferred.
PKE -- Parameter ID (1
st
and 2
nd
octet).
IND -- Sub-index (3
rd
octet), 4
th
octet is reserved.
PWE -- Parameter value (5
th
to 8
th
octet, 32-bits).
STW -- Control word.
ZSW -- Status word.
HSW -- Main reference.
HIW -- Main actual value.