APPENDIX PARAMETER CROSS-REFERENCE LIST
22
Parameter cross-reference list
To be able to read/write parameters via Profibus it is necessary to use a cross-reference list to convert from
Profibus parameters to actual parameter values in the inverter.
Example, if parameter “1st Acceleration time 1” shall be read then parameter number 23 shall be used (if the
keypad is used F002 is used).
The L300P inverter supports a slightly different parameter map; the “L300P” field reflects this. “No” means
that the L300P inverter does not support the parameter, a figure means that the parameter is supported, but
with this maximum value instead.
Code No. Size Range Magn. Contents L300P
Read/
Write
A020
14
0 400.00Hz
*100 1st setting Multispeed frequency 0 R/W
A220 2 4
0 400.00Hz
*100 2nd setting Multispeed frequency 0 R/W
A320 3 4
0 400.00Hz
*100 3rd setting Multispeed frequency 0 No R/W
A021 4 4
0 400.00Hz
*100 Multispeed frequency 1 R/W
A022 5 4
0 400.00Hz
*100 Multispeed frequency 2 R/W
A023 6 4
0 400.00Hz
*100 Multispeed frequency 3 R/W
A024 7 4
0 400.00Hz
*100 Multispeed frequency 4 R/W
A025 8 4
0 400.00Hz
*100 Multispeed frequency 5 R/W
A026 9 4
0 400.00Hz
*100 Multispeed frequency 6 R/W
A027 10 4
0 400.00Hz
*100 Multispeed frequency 7 R/W
A028 11 4
0 400.00Hz
*100 Multispeed frequency 8 R/W
A029 12 4
0 400.00Hz
*100 Multispeed frequency 9 R/W
A030 13 4
0 400.00Hz
*100 Multispeed frequency 10 R/W
A031 14 4
0 400.00Hz
*100 Multispeed frequency 11 R/W
A032 15 4
0 400.00Hz
*100 Multispeed frequency 12 R/W
A033 16 4
0 400.00Hz
*100 Multispeed frequency 13 R/W
A034 17 4
0 400.00Hz
*100 Multispeed frequency 14 R/W
A035 18 4
0 400.00Hz
*100 Multispeed frequency 15 R/W
A061 19 4
0 400.00Hz
*100 1st Upper limiter frequency R/WOS
A261 20 4
0 400.00Hz
*100 2nd Upper limiter frequency R/WOS
A062 21 4
0 400.00Hz
*100 1st Lower limiter frequency R/WOS
A262 22 4
0 400.00Hz
*100 2nd Lower limiter frequency R/WOS
F002 23 4
0.01 3600.00s
*100 1st Acceleration time 1 R/W
F202 24 4
0.01 3600.00s
*100 2nd Acceleration time 1 R/W
F302 25 4
0.01 3600.00s
*100 3rd Acceleration time 1 No R/W
F003 26 4
0.01 3600.00s
*100 1st Deceleration time 1 R/W
F203 27 4
0.01 3600.00s
*100 2nd Deceleration time 1 R/W
F303 28 4
0.01 3600.00s
*100 3rd Deceleration time 1 No R/W
A092 30 4
0.01 3600.00s
*100 1st Acceleration time 2 R/W
A292 31 4
0.01 3600.00s
*100 2nd Acceleration time 2 R/W
A392 32 4
0.01 3600.00s
*100 3rd Acceleration time 2 No R/W
A093 33 4
0.01 3600.00s
*100 1st Deceleration time 2 R/W
A293 34 4
0.01 3600.00s
*100 2nd Deceleration time 2 R/W
A393 35 4
0.01 3600.00s
*100 3rd Deceleration time 2 No R/WOS