IBM SCOD-3ZVQ5W Server User Manual


 
Chapter 55. xSeries rack power configurator 479
Typical Rack Power Configurations
Notes:
1. Each PDU and UPS comes with a country-specific power cord.
2. One 2m internal rack power cable provided with DPI Rack PDU.
3. Line cord provided with Front-end PDU.
Attention: Customers are responsible for providing a dedicated circuit for each line cord protected with an
appropriate circuit breaker.
Rack Rules and PDU Capacities
NetBay and DPI PDUs cannot be mixed in the same side-wall compartment.
DPI Rack PDUs can be cabled to NetBay Front-end PDUs.
PDUs per Rack Standard Enterprise
25U 42U 9308
2-bay 2-bay 2-bay 3-bay 4-bay
Rack PDUs488812
Front-end PDUs24244
Enterprise PDUs24244
High Density
PDUs
24444
Total PDUs 4 12 8 12 16
Redundant:
six Rack PDUs
and two Front-end PDUs
(dual circuit, 42 outlets)
Simple:
three Rack PDUs
and one Front-end PDU
(single circuit, 21 outlets)
Simple:
two Rack PDUs
(two circuits, 14 outlets)
(2)
Rack
Cabinet
(3)
P
D
U
P
D
U
P
D
U
F
E
P
D
U
P
D
U
P
D
U
F
E
Rack
Cabinet
P
D
U
P
D
U
(1)
Rack PDU
7 outlets - C13
1 inlet - C20
(2)
Rack
Cabinet
(3)
P
D
U
P
D
U
P
D
U
F
E
Front-end PDU
3 outlets - C19
1 inlet - hardwired
Simple:
one Enterprise PDU
(single circuit, 6 or 12 outlets)
Rack
Cabinet
E
-
P
D
U
(1)
Enterprise PDU
12 outlets - C13
or 6 outlets - C19
1 inlet - hardwired
or pluggable