Appendix C. UPS runtime estimate (minutes) 511
Notes:
1. Data provided by Eaton.
Table 147. IBM UPS3000HV Runtimes
1
Number of Battery Packs
+0 +1 +2 +3 +4
Total Load
(Watts)
Runtime
(Hours / Minutes)
Runtime
(Hours/ Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
200 1/3 4/38 9/5 12/48 16/42
300 55 4/5 8/0 11/16 14/42
400 48 3/33 6/59 9/59 12/50
500 42 3/6 6/4 8/33 11/10
600 36 2/38 5/10 7/17 9/30
700 31 2/14 4/23 6/11 8/4
800 26 1/56 3/48 5/22 7/0
900 23 1/40 3/16 4/36 6/0
1000 19 1/23 2/44 3/51 5/2
1100 16 1/12 2/22 3/20 4/22
1200 14 1/3 2/4 2/54 3/48
1300 12 55 1/48 2/33 3/20
1400 10 47 1/32 2/10 2/50
1500 9 45 1/28 2/4 2/42
1600 9 41 1/20 1/53 2/28
1700 8 40 1/18 1/50 2/24
1800 8 40 1/18 1/50 2/24
1900 7 35 1/8 1/36 2/6
2000 7 35 1/8 1/36 2/6
2100 7 33 1/5 1/32 2/0
2200 6 30 58 1/22 1/48
2300 6 30 58 1/22 1/48
2400 6 30 58 1/22 1/48
2500 6 26 51 1/12 1/34
2600 5 25 49 1/9 1/30
2700 5 25 49 1/9 1/30