510 COG
2. Battery output may be set to 220, 225, 230 or 240 VAC.
3. Country-specific line cords available as options.
Notes:
1. Data provided by Eaton.
Table 146. IBM UPS3000LV Runtimes
1
Number of Battery Packs
+0 +1 +2 +3 +4
Total Load
(Watts)
Runtime
(Hours / Minutes)
Runtime
(Hours/ Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
Runtime
(Hours / Minutes)
200 1/3 5/16 7/57 11/15 14/34
300 55 4/35 7/0 9/55 12/50
400 48 4/1 6/6 8/39 11/12
500 42 3/31 5/19 7/31 9/44
600 36 3/3 4/31 6/24 8/17
700 31 2/35 3/50 5/26 7/2
800 26 2/12 3/20 4/43 6/6
900 23 1/55 2/51 4/2 5/14
1000 19 1/38 2/23 3/23 4/23
1100 16 1/22 2/4 2/56 3/48
1200 14 1/11 1/48 2/33 3/19
1300 12 1/2 1/35 2/14 2/54
1400 10 54 1/20 1/54 2/28
1500 9 46 1/11 1/41 2/10
1600 8 41 1/8 1/37 2/5
1700 8 40 1/8 1/37 2/5
1800 8 40 1/8 1/37 2/5
1900 7 39 1/0 1/25 1/50
2000 7 35 1/0 1/25 1/50
2100 7 33 1/0 1/25 1/50