Appendix C. UPS runtime estimate (minutes) 513
Notes:
1. Data provided by APC.
Table 149. IBM UPS7500XHV, 10000XHV Runtimes
1
Number of Battery Packs
+0 +1 +2 +4
Total Load (Watts)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
Runtime
(Hours/Minutes)
200 4/6 7/36 11/54 20/54
300 3/6 5/48 9/6 16/0
400 2/30 4/36 7/18 12/48
500 2/6 3/54 6/6 10/42
600 1/48 3/18 5/12 9/12
700 1/30 2/54 4/30 8/0
800 1/18 2/30 4/0 7/0
900 1/12 2/18 3/36 6/12
1000 1/6 2/0 3/12 5/42
1200 55 1/42 2/42 4/48
1400 47 1/30 2/18 4/6
1600 41 1/12 2/0 3/36
1800 36 1/6 1/48 3/12
2000 32 1/0 1/36 2/54
3000 19 39 1/0 1/48
4000 13 28 46 1/18
5000 10 21 35 1/0
6000 7 16 28 52
7000 5 13 23 44
8000 4 11 20 37
Note: UPS7500 is rated for up to 6000 total watts; UPS10000 is rated for up to 8000 total watts.