IBM SCOD-3ZVQ5W Server User Manual


 
Chapter 55. xSeries rack power configurator 481
Country-specific considerations: USA, Canada, parts of Latin America,
Taiwan
Power Load Capacity
Part
Number
Plug Type Source Circuit
(single phase 50/60Hz)
PDU Output
(single phase 50/60Hz)
32P1761 NEMA L5-15P 100-127Vac, 15a
six 100-127Vac, NEMA5-15R
receptacles, shared
12a
NEMAL5-20P 100-127Vac, 20a seven 100-127Vac, shared 15a
NEMAL6-20P 200-240Vac, 20a seven 200-240Vac, shared 15a
32P1736
Part
Number
Plug Type Source Circuit (50/60Hz) PDU Output
(single phase 50/60Hz)
32P1751 NEMA L5-30P 100-127Vac, 30a,
single-phase
three 100-127Vac, 20a each, shared
24a
32P1766 NEMA L6-30P 208Vac, 30a, single-phase
line-to-line with ground
three 208Vac, 20a each, share
d 24a
32P1767 IEC 309-2P+G 208Vac, 60a, single-phase
line-to-line with ground
three 208Vac, 20a each, shared
48a
Part
Number
Plug Type Source Circuit (50/60Hz) PDUOutput
(single phase 50/60Hz)
73P5855 IEC 309 2P+G 208Vac, 60a, single-phase
dedicated circuit
twelve 208Vac, 16a each, shared
48a
73P5847 IEC 309 3P+G 208Vac, 60a, three-phase
delta dedicated circuit
twelve 208Vac, 16a each, shared
28a per four outlet phase group
Rack PDUs
Front-end PDUs
High Density PDUs
Enterprise PDUs
Part
Number
Plug Type Source Circuit (50/60Hz) PDU Output
(single phase 50/60Hz)
26K42
46 NEMA L6-30P 208Vac, 30a, single-phase
dedicated circuit
twelve 208Vac, 10a each, shared
24a
26K4242 IEC 309 2P+G 208Vac, 60a, single-phase
dedicated circuit
twelve 208Vac, 10a each, shared
48a
26K4244 IEC 309 3P+G 208Vac, 60a, three-phase
delta dedicated circuit
twelve 208Vac, 10a each, shared
28a per four outlet phase group
26K4256 IEC 309 2P+G 208Vac, 60a, single-phase
dedicated circuit
six 208Vac, 16a each, shared 48a
26K4258 IEC 309 3P+G 208Vac, 60a, three-phase
delta dedicated circuit
six 208Vac, 16a each, shared 28a
per two outlet phase group
(2) Line Cords: Rack PDU
(5) Line Cords: Front-end
PDU
Power Cables:
(1) Device to Rack PDU or Enterprise C13 PDU power cable
IEC C13 to C14, 10/15a cable
typical: 36L8886 (2.8m)
requirement: C14 plug, long enough to reach
available option: 94G7448 (14ft)
(2) Rack PDU to wall line cord
IEC C19 to country-specific connector, 16/20a, 14ft (4.3m)
(3) Rack PDU to UPS power cable
IEC C19 to C20, 16/20a
00N7700 (2m)
provided with 37L6861 APC SU-5000RMB
(4) Rack PDU to Front-end PDU power cable
IEC C19 to C20, 16/20a
00N7698 (1m) provided with the NetBAY Front-end PDUs
00N7700 (2m) provided with the DPI Front-end PDUs
(5) Front-end PDU to wall line cord
hardwired to country-specific connector, 30/32a, 60/63a, 8.2ft
(2.5m)
(7) Device to High Density PDU power cable
IEC C19 to C20, 16/20a, 2.5m
(8) Enterprise PDU to wall line cord
hardwired or pluggable to country-specific connector, 30/60a, 14ft
(4.3m)
(9) High Density PDU to wall line cord
hardwired or plugugable to country-specific connector, 60a, 8.2ft
(2.5m)
(10) Device to FE-, E-, or HD-PDU power cable
IEC C13 to C20, 10/15a cable
option: 23K4809 9ft (2.8m)
(9) Line Cords:High Density PDU
(8) Line Cords:Enterprise PDU