Liebert 30-130kVA Power Supply User Manual


 
Operation
24
Detailed Information Reports
Detailed information reports are available through the following numbered blocks
1. INPUT STATUS. To access this screen, start with the Mimic Display Screen. Using the arrow
keys, bracket INPUT and press SELECT. The screen displays the UPS input voltage and current
as well as additional information. Press SELECT to return to the Mimic Display Screen.
Figure 15 Input status screen
The Input Status screen displays the following real-time data:
Input AC Volts AB, BC, CA
Input Current A, B, C
Input Frequency
Inlet Air Temperature
Outlet Air Temperature
Heat Sink Temperature (100 and 130 kVA will display 3 temperatures, 1 for each heatsink)
2. DC BUS / BATTERY. By highlighting and selecting BATTERY from the Mimic Display Screen,
the following screen comes up, displaying DC bus voltage and the charge or discharge current.
This screen also shows BATTERY TEMPERATURE. Press SELECT to return to the Mimic
Display Screen.
Figure 16 DC bus / battery status
NOTE
On the Mimic Display Screen, items are bracketed instead of highlighted so as not to confuse
highlighting with power pathways.
NOTE
All voltage readings are phase-to-phase measurements (A-B, B-C, and C-A). All current
readings are phase measurements (A, B, and C). The metered parameter values on the
following screens are updated at one-second intervals
INPUT STATUS
A B C FREQ. 60.0 HZ
V L - L 209 209 210 TEMPS (DEG C)
I 37 37 35 INLET AIR 24
OUTLET AIR 27
HEAT SINKS
1:025 2:020 3:020
DC BUS / BATTERY STATUS
DC BUS VOLT 540
BATT VOLT 472
BATT CURR 4.1 (CHG)
BATT TEMP 25
LAST BATTERY TEST : 07/07/02
NUMBER OF BATT. ONLINE 1
C