Liebert 30-130kVA Power Supply User Manual


 
Operation
88
3.4.3 Status
Status conditions give the Operator additional knowledge about UPS operation. Some are indicated
on the Mimic Display screen by a text message while others are depicted graphically.
The following status messages may appear in the Operator display.
Static Switch Connected. The static switch is connected (the disconnect switches are closed - ON)
and is ready to provide a current path from the bypass input to the load.
Static Switch Disconnected. The static switch is disconnected (the disconnect switches are open -
OFF) for maintenance procedures.
OK to Transfer. The UPS system voltage, frequency, and phase match the bypass line. This
means that a transfer between the bypass line and the UPS is permitted.
Not OK to Transfer. Either the UPS or bypass voltage, frequency, or phase is not within the spec-
ified limits or the static bypass switch is not available. Therefore, manually-initiated transfer
between the bypass line and the UPS is not permitted. Emergency or overload transfer to bypass
may still be available provided the “Static Switch Unable” alarm is not indicating.
Time to Overload Transfer. During an overload condition, the time remaining before transfer (in
seconds) is displayed at the bottom of the load block.
3.5 Communication Interfaces
The Npower UPS can be configured with various communication ports to assist the Operator in moni-
toring the UPS system.
Input Contact
#4
Input Contact
#4
Alarm YES YES NO YES
The System has been notified from the OC-
DI option that a customer alarm has been
activated. The system will substitute user-
defined text when displaying these alarms.
Input Contact
#5
Input Contact
#5
Alarm YES YES NO YES
The System has been notified from the OC-
DI option that a customer alarm has been
activated. The system will substitute user-
defined text when displaying these alarms.
Input Contact
#6
Input Contact
#6
Alarm YES YES NO YES
The System has been notified from the OC-
DI option that a customer alarm has been
activated. The system will substitute user-
defined text when displaying these alarms.
Input Contact
#7
Input Contact
#7
Alarm YES YES NO YES
The System has been notified from the OC-
DI option that a customer alarm has been
activated. The system will substitute user-
defined text when displaying these alarms.
Input Contact
#8
Input Contact
#8
Alarm YES YES NO YES
The System has been notified from the OC-
DI option that a customer alarm has been
activated. The system will substitute user-
defined text when displaying these alarms.
NOTE
There are 8 alarms on the Remote Alarm Status Panel. See 3.5.3 - Remote Alarm Status
Panel
Table 7 Alarms, functions, and corrective actions (continued)
Actual
Alarm/fault
Name
Displayed
On Front
Panel
Description
of Alarm/
Fault
Fault
Or
Alarm
Latch
Mask
Dial
Mask
Freeze
Mask
Event Log
Mask Meaning and Corrective Action(s)