Operation
43
Options
This multiple-page screen, accessed from the third page of the SYSTEM SETTINGS screen, enables
and disables optional features which might or might not be installed in your UPS. To enable or dis-
able one of these options, do the following:
1. Highlight the option you wish to enable or disable.
2. Press UP or DOWN to toggle between enabled or disabled.
3. Press SELECT to set the desired status.
Figure 50 Options screen, page 1
Highlighting 10% PASSIVE OPTIONS and pressing SELECT will bring up the following screen
allowing the Operator to decide whether or not the input trap filter should be disconnected at light
loads to prevent a leading power factor at the input. For more information, see Input Trap Filter in
the options manual.
Figure 51 10% passive filter settings screen
NOTE
Some of the options appearing on the following screens are reserved for future development.
OPTIONS
ACTIVE FILTER NO
LBS NO
GENERATOR NO
AUTO RESTART NO
NEXT
EXIT
NEXT
FILTER DISCONNECT LEVEL 0
FILTER PREFERRED STATE CLOSED
10% PASSIVE FILTER CONTACTOR DISABLE
10% PASSIVE FILTER SETTINGS
EXIT