Operation
50
Figure 69 Factory settings screen, page 2
Figure 70 Factory settings screen, page 3
Alarm Mask
The Alarm Mask sets parameters for all alarms that affect the UPS and output channels. The pro-
grammable attributes are described below. The letters L, D, F and E in Figure 71 refer to these fea-
tures, allowing the operator to determine their status.
Latching
This option latches the alarm when it occurs. Latching alarms will not automatically clear from the
screen when the alarm condition ends, and must be cleared from the screen by the operator.
Dial
When an alarm condition occurs, and the system has an Auto Dial option, the system will dial out to a
designated number in accordance with the Dial Out (Auto Dial) instructions set in the UPS. See
AUTO DIAL on page 52 for more information on this feature.
Freeze
This feature will freeze the History Log Buffer(s) if an alarm is detected. This feature is used mainly
for diagnostic purpose by Liebert Global Services and Engineering.
Event Logging
The list of alarms that can be masked are shown in Table 7. Most Events are automatically logged
into the Event History Buffer. Events that can be selected or deselected by the user are:
Input Line Fail
Input Under Voltage
Input Over Voltage
Bypass Sync Error
Bypass Voltage Out of Tolerance
Bypass Line Fail
Input Contact Alarms (if this option is installed)
INVERTER DC OFFSET PHASE B
INVERTER DC OFFSET PHASE C
INPUT I LIMIT WITH TRAP 164.1
INPUT I LIMIT WITHOUT TRAP 190.8
INPUT I LIMIT ON GENERATOR 100
FACTORY SETTINGS
SAVE & EXIT
CANCEL
NEXT
PREV.
NEXT
INPUT PID LOOP
ON GENERATOR DELAYED RESTART 10
BYPASS / OUTPUT PHASING 30
FACTORY SETTINGS
SAVE & EXIT
CANCEL
PREV.