Liebert 30-130kVA Power Supply User Manual


 
Operation
29
Manual Startup
On occasion, a service technician may wish to start the UPS manually while performing diagnostic
testing. The manual startup, like the auto startup, requires that the Rotary Switch be in the NOR-
MAL position. To start the system manually, highlight MANUAL STARTUP and press the SELECT
button on the navigation bar. This action brings up the MIMIC DISPLAY screen, prompting the
Operator to close the Static Switch contactors.
Figure 24 Manual startup screen, close static switch contactors screen
Press OK to close the SS contactors, turning on the Static Switch. Press SKIP only to proceed without
closing the Static Switch contactors. Either selection brings up the screen enabling modification of
input current limit.
Figure 25 Target and ramp values
Press SKIP to proceed or OK to change values. If Operator selects SKIP, the Mimic Display screen is
momentarily displayed, followed by the screen enabling modification of DC Bus Setpoint.
Figure 26 DC bus setpoint screen
MIMIC DISPLAY
BATTERY
INV.
LOAD
RECT.
SS
SERV
OK
A
BORT
SKIP
INPUT
OK
SKIP
MODIFY CURRENT LIMIT
TARGET AND RAMP VALUES
TARGET (A) : 13
RAMP (S) : 10
MODIFY DC BUS SET POINT
TARGET AND RAMP VALUES
TARGET (V) 540