Operation
37
The second page is the STATUS, which includes:
• Static Bypass Switch Line (Open/Closed)
• Static Bypass Switch Load (Open/Closed)
• Input Contactor (Open/Closed)
• Output Contactor (Open/Closed)
• Trap Filter (On/Off) (If installed)
• Int. MBP (Normal/Bypass Service)
• Ext. MBP (Open/Closed)
• Battery CB (Open/Closed)
•SBS (On/Off)
• Rectifier (On/Off)
• Inverter (On/Off)
Figure 38 History log status report screen
The last page includes faults. The alarm conditions that cause the History Status buffer to store and
freeze data are:
• Rectifier fail
• Battery Low Transfer
• Output Overvoltage Transfer
• Output Undervoltage Transfer
•Inverter Fail
• Inverter Overload Transfer
• Heatsink Overtemp Limit
• Outlet Air Overtemp Limit
• Fault Load Transfer to Bypass
• Transfer Failed Shutdown
Figure 39 History log faults/alarms report screen
HISTORY LOG 1 P2 - STATUS
14 : 19: 50 02 / 10 / 00
EXITMETER
PREV
NEXT
ALARMS
FRAME 0
SBS LINE
SBS LOAD
INP DELTA
OUTPUT
TRAP
INT. MBP SERVICE
EXT. MBP OPEN
BATT CB OPEN
SBS OFF
RECT. OFF
INV. OFF
HISTORY LOG 1 P3 - FAULTS / ALARMS
14 : 22: 29 02 / 10 / 00
EXITSTATUS
PREVNEXT
METER
FRAME 40
INPUT OF / UF
DC OV TRANSIENT
RECTIFIER FUSE FAIL
INPUT OF / UF