The following faults are detected by the UPS controls. Corrective actions, where possible, are auto-
matic.
Active Filter Fail
Battery Overtemp CB Trip
Battery Ground Fault CB Trip
Bypass Power Supply Fail
EPO Shutdown
Heatsink Overtemp Limit
Input Power Supply Fail
Output Power Supply Fail
Outlet Air Overtemp Limit
Power Supply F1 Fail
SWGR Power Fail
DC Undervoltage Steady State
DC Overvoltage Steady State
Rectifier Fail
•Inverter Fail
Overtemp Time out Shutdown
Fault Transfer Failed - Shutdown
Controller Fault -SBS on.
Hardware Shutdown.
MM Control Power Fail.
MM Memory Fail.
Option Power Supply Fail
3.4.2 Alarms
An alarm is an indication of an abnormal system condition significant enough to warrant being
annunciated and logged. Alarm conditions may indicate that a UPS system parameter is out of its
normal operating range, or may signal an external problem. In some cases an alarm may trigger a
corrective action. Many alarm conditions will return to normal in due time and the alarm itself will no
longer be “active.”
Summary Alarm
The Npower system features a Summary Alarm, which captures the presence of individual faults and
alarms. This alarm may be assigned to any PRB relay. See Customer Alarm Interface on page 52.
The Summary Alarm can be accessed from the list of alarms / faults (Figure 80) by scrolling up and
down the list. (For navigation instructions, see Customer Alarm Interface on page 52). When the
Summary Alarm is in the active position, it will be flashing at the top of the screen.
Figure 109Summary alarm in active position screen
ALARM / FAULT NAME
L D F E DELAY
Y Y N Y 55.15
ON BATTERY Y Y Y Y 0 0
INPUT CONTACT #1 Y Y Y Y 0 0
INPUT CONTACT # 2 Y Y Y Y 0 0
INPUT CONTACT # 3 Y N Y Y 0 0
INPUT CONTACT # 4 Y Y Y Y 0 0
DOWN
UP EXIT DESCRIPTION: L - Latching...D - Dial...