options
extended battery cabinet
As standard equipment, Comet comes with a battery providing a backup time (at
full rated load and a power factor of 0.6) of 8 minutes for the 5 kVA Comet S11
and S31 and 10 minutes for the other Comet models. This time can be increased
by installing 1 or 2 additional battery cabinets.
If Comet was not factory-set for the additional cabinets, the new configuration
must be entered by a MGE UPS SYSTEMS after-sales support technician.
Battery cells for an overall operating range of 30 mn
(at rated output power with a power factor of 0.6):
Comet Battery cell rated output of device (kVA)
characterisitics 5 7,5 10 15 20 30
series 11 height (mm) 730 910 910
width (mm) 360 400 400
depth (mm) 420 550 550
weight (kg) 72 118 149
series 31 height (mm) 730 910 910 1085 1085
width (mm) 360 400 400 560 560
depth (mm) 420 550 550 680 680
weight (kg) 72 118 149 270 340
series 33 height (mm) 1085 1085 1385 1385
width (mm) 460 560 610 610
depth (mm) 680 680 780 780
weight (kg) 176 270 355 480
Comet Battery cell rated output of device (kVA)
characterisitics 5 7,5 10 15 20 30
series 11 height (mm) 730 910 910
width (mm) 360 400 400
depth (mm) 420 550 550
weight (kg) 115 215 276
series 31 height (mm) 730 910 910 1085 1085
width (mm) 360 400 400 2 x 560 2 x 560
depth (mm) 420 550 550 680 680
weight (kg) 115 215 276 2 x 270 2 x 340
series 33 height (mm) 1085 1085 1385 1385
width (mm) 460 2 x 560 2 x 610 2 x 610
depth (mm) 680 680 780 780
weight (kg) 281 2 x 270 2 x 355 2 x 480
Battery cells for an overall operating range of 50 mn
(at rated output power with a power factor of 0.6):
additional battery cell characterisitics