Comet installation and user manual: E-6761200XT/FB
11.2
Merlin Gerin by MGE UPS SYSTEMS
Comet series 11 general characteristics
■ apparent power (kVA): 5 7.5 10
■ active power (kW): 4 6 8
■ efficiency (%): 91 91 91
■ heat losses (W): 445 668 890
■ noise level (dBa):
■■ on RL load: 45 46 46
■■ on RCD load: 50 53 53
■ battery backup time (minutes):
■■ at rated load (power factor 0.6): 8 10 10
■ maximum leakage current (mA):
■■ directly earthed neutral system (TT): 10 23 23
■■ during a fault with an impedent neutral system: 28 60 60
■ dimensions and weight
■ ■ height (mm): 730 910 910
■ ■ width (mm): 360 400 400
■ ■ depth (mm): 420 550 550
■ ■ weight (kg): 90 190 210
■ AC input
■■ number of phases: 1
■■ voltage (V): 187 to 257
■■ frequency (Hz): 47 to 63
■■ power factor: > 0.99
■■ current distortion (%): < 5 < 3 < 3
■■ inrush current: < In
■ AC output
■■ number of phases: 1
■■ voltage (V): 220 / 230 / 240
■■ voltage tolerance (%): ± 1
■■ frequency (Hz): 50 / 60
■■ frequency tolerance (free-running) (%): ± 0.1
■■ frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4
■■ synchronization rate (Hz/s): 1 / 2
appendices (cont')