MGE UPS Systems Comet TM 5 - 30 kVA Power Supply User Manual


 
Comet installation and user manual: E-6761200XT/FB
11.2
Merlin Gerin by MGE UPS SYSTEMS
Comet series 11 general characteristics
apparent power (kVA): 5 7.5 10
active power (kW): 4 6 8
efficiency (%): 91 91 91
heat losses (W): 445 668 890
noise level (dBa):
on RL load: 45 46 46
on RCD load: 50 53 53
battery backup time (minutes):
at rated load (power factor 0.6): 8 10 10
maximum leakage current (mA):
directly earthed neutral system (TT): 10 23 23
during a fault with an impedent neutral system: 28 60 60
dimensions and weight
height (mm): 730 910 910
width (mm): 360 400 400
depth (mm): 420 550 550
weight (kg): 90 190 210
AC input
number of phases: 1
voltage (V): 187 to 257
frequency (Hz): 47 to 63
power factor: > 0.99
current distortion (%): < 5 < 3 < 3
inrush current: < In
AC output
number of phases: 1
voltage (V): 220 / 230 / 240
voltage tolerance (%): ± 1
frequency (Hz): 50 / 60
frequency tolerance (free-running) (%): ± 0.1
frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4
synchronization rate (Hz/s): 1 / 2
appendices (cont')