Comet series 31 general characteristics
■ apparent power (kVA): 5 7.5 10 15 20
■ active power (kW): 4 6 8 12 16
■ efficiency (%): 91 91 91 92 92
■ heat losses (W): 445 668 890 1335 1780
■ noise level (dBa):
■■ on RL load: 45 46 46 50 50
■■ on RCD load: 50 53 53 53 53
■ battery backup time (minutes):
■■ at rated load (power factor 0.6): 8 10 10 10 10
■ maximum leakage current (mA):
■■ directly earthed neutral system (TT): 5 11 11 24 24
■■ during a fault with an impedent neutral system: 23 45 45 102 102
■ dimensions and weight
■ ■ height (mm): 730 910 910 1085 1085
■ ■ width (mm): 360 400 400 560 560
■ ■ depth (mm): 420 550 550 680 680
■ ■ weight (kg): 90 190 210 390 450
■ AC input
■■ number of phases: 3
■■ voltage (V): 323 to 444
■■ frequency (Hz): 47 to 63
■■ power factor: > 0.95
■■ current distortion (%): < 26
■■ inrush current: < In
■ AC output
■■ number of phases: 1
■■ voltage (V): 220 / 230 / 240
■■ voltage tolerance (%): ± 1
■■ frequency (Hz): 50 / 60
■■ frequency tolerance (free-running) (%): ± 0.1
■■ frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4
■■ synchronization rate (Hz/s): 1 / 2