MGE UPS Systems Comet TM 5 - 30 kVA Power Supply User Manual


 
Comet installation and user manual: E-6761200XT/FB
11.3Merlin Gerin by MGE UPS SYSTEMS
Comet series 31 general characteristics
apparent power (kVA): 5 7.5 10 15 20
active power (kW): 4 6 8 12 16
efficiency (%): 91 91 91 92 92
heat losses (W): 445 668 890 1335 1780
noise level (dBa):
on RL load: 45 46 46 50 50
on RCD load: 50 53 53 53 53
battery backup time (minutes):
at rated load (power factor 0.6): 8 10 10 10 10
maximum leakage current (mA):
directly earthed neutral system (TT): 5 11 11 24 24
during a fault with an impedent neutral system: 23 45 45 102 102
dimensions and weight
height (mm): 730 910 910 1085 1085
width (mm): 360 400 400 560 560
depth (mm): 420 550 550 680 680
weight (kg): 90 190 210 390 450
AC input
number of phases: 3
voltage (V): 323 to 444
frequency (Hz): 47 to 63
power factor: > 0.95
current distortion (%): < 26
inrush current: < In
AC output
number of phases: 1
voltage (V): 220 / 230 / 240
voltage tolerance (%): ± 1
frequency (Hz): 50 / 60
frequency tolerance (free-running) (%): ± 0.1
frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4
synchronization rate (Hz/s): 1 / 2