MGE UPS Systems Comet TM 5 - 30 kVA Power Supply User Manual


 
Comet installation and user manual: E-6761200XT/FB
11.4
Merlin Gerin by MGE UPS SYSTEMS
Comet series 33 general characteristics
apparent power (kVA): 10 15 20 30
active power (kW): 8 12 16 24
efficiency (%): 92 92 92 92
heat losses (W): 890 1335 1780 2670
noise level (dBa):
on RL load: 51 51 51 51
on RCD load: 52 52 52 52
battery backup time (minutes):
at rated load (power factor 0.6): 10 10 10 10
maximum leakage current (mA):
directly earthed neutral system (TT): 23 23 23 23
during a fault with an impedent neutral system: 90 90 250 250
dimensions and weight
height (mm): 1085 1085 1385 1385
width (mm): 460 460 610 610
depth (mm): 680 680 780 780
weight (kg): 275 350 510 600
AC input
number of phases: 3
voltage (V): 323 to 444
frequency (Hz): 47 to 63
power factor: > 0.95
current distortion (%): < 26
inrush current: < In
AC output
number of phases: 3
voltage (V): 380 / 400 / 415
voltage tolerance (%): ± 1
frequency (Hz): 50 / 60
frequency tolerance (free-running) (%): ± 0.1
frequency tolerance (synchronized) (%): ± 1 / ± 1.5 / ± 2 / ± 3 / ± 4
synchronization rate (Hz/s): 1 / 2
appendices (cont')