Microtest TSB-67 - 568A Annex E Scanner User Manual


 
Frequency range
PentaScanner+
: 1.0 to 100 MHz
PentaScanner
/
PentaScanner
Cable Admin
: 1.0 to 100 MHz
Sweep mode: Swept 1- 100 MHz using 1 MHz step or fixed points (1.0, 2.0, 4.0,5,0, 8.0,
10, 16.0, 20, 25, 31.25, 62.5, and 100 MHz)
Dynamic Range: 0 - 50 dB
Measurement Accuracy:
PentaScanner+
: Calculated per TIA TSB-67 error model (see NEXT and Attenuation
Specifications table)
PentaScanner
/
PentaScanner
Cable Admin
: 1.5 dB
Measurement resolution: 0.1 dB
Impedance
Range: 40 to 200 ohms
Accuracy: ± 5 ohms
Resolution: 2 ohms
Loop Resistance
Range: 0 to 10000 ohms
Accuracy: ± 0.3 ohms @ 0 to 15 ohms
± 2% @ 15 to 109 ohms (
PentaScanner+
)
± 2% @ 15 to 200 ohms (
PentaScanner
/
PentaScanner
Cable Admin
± 5% @ 109 to 5000 ohms (
PentaScanner+
)
± 5% @ 200 to 5000 ohms (
PentaScanner
/
PentaScanner
Cable
Admin
)
± 10% @ 5000 to 10000 ohms
Resolution: 0.1 ohms 0 to 200 ohms
1.0 ohms 200 to 9.999K ohms
Capacitance
Range: 0 to 100,000 pF
Accuracy: ± 20 pF 0 to 200 pF
± 10% 200 to 100,000 pF
Resolution: 5 pF 20 to 1000 pF
50 pF 1000 to 100,000 pF
Impulse Noise
Detects the occurrence of narrow impulse type events exceeding an adjustable threshold of
± 0.262, 0.524, 1.0, 2.0 or 2.5 volts. Instantly displays up to 200 impulse noise events per
second. Graphically logs and displays impulse events for up to 25 hours. Termination
impedance: 200 ohms.
Peak to Peak Noise
Measures the peak to peak voltage of steady state noise signals.
Range: 0 to 3,000 mVpp into 100 ohms.
Bandwidth: 3dB from 40 kHz to 30 MHz