Nortel Networks 15000 Network Router User Manual


 
Installing the Versalar 15000
308684-B Rev 00
2-13
Mounting the Versalar 15000 in a 19-Inch Rack
To install the Versalar 15000 in a 19-inch four-post rack:
1.
Measure at least 27 in. (68.6 cm) of free vertical space inside the rack and
mark the spot.
2.
Mount the angle brackets in the area indicated in Figure 2-4.
3.
If the holes in the rack’s vertical supports are not threaded for cagenut
screws, insert a cagenut in five locations (Figure 2-4)
.
4.
Holding the Versalar 15000 in position, align the flanged end of each
bracket with two holes on each side of the vertical rack support.
It is easiest to complete this step with two people. Make sure that the hole
pairs on either side of the vertical support match horizontally.
5.
Insert a cagenut screw through each flange hole and into the
corresponding hole in the rack (Figure 2-5)
.
6.
Tighten each cagenut screw with a Phillips screwdriver.