Omron CS1W-RPT01 Network Card User Manual


 
83
Constructing Networks with Repeater Units Section 3-4
Partial Conversion to Optical Fiber
Combining T-Branch Wiring (2-stage Repeater) and Partial Optical Fiber
Note When constructing a network using Repeater Units, each segment must sat-
isfy all of the following requirements:
The total number of Controller Link Units, Support Boards, and Repeater
Units within a single segment must not exceed 32.
The total cable length of a single segment must not exceed the specified
value. (500 m at 2 Mbps; 800 m at 1 Mbps; and 1 km at 500 Kbps.)
The maximum number of repeater stages that can be inserted into the
path connecting any two nodes is two.
The node at each end of a segment (including Repeater Units) must have
terminating resistance turned ON.
The baud rates within each segment must be set to the same value.
Terminating
Resistance: ON
Segment 1 Segment 2
Terminating
Resistance: ON
Terminating
Resistance: ON
Terminating
Resistance: ON
(Optical fiber cable)
Repeater Unit
CS1W-RPT02 or
CS1W-RPT03
Segment 1
Segment 2
Terminating
resistance: ON
CS1W-RPT02 or
CS1W-RPT03
Repeater Unit
Terminating
resistance: ON
Terminating
resistance: ON
Terminating
resistance: ON
Terminating
resistance: ON
Terminating
resistance: ON
Terminating
resistance: ON
Terminating
resistance: ON
Segment 3
Segment 4
CS1W-RPT01
Repeater Unit