Omron CS1W-RPT01 Network Card User Manual


 
63
Unit Installation Section 3-2
CJ-series PLCs
Up to a total of four Controller Link Units for CJ-series PLCs can be connected
in a CPU Rack or a Expansion Rack. (Be sure to secure the Units with the top
and bottom sliders.)
Note When installing several CJ-series CPU Bus Units at the same time, a total of
16 CJ-series CPU Bus Units maximum may be installed.
Up to eight CS/CJ-series Controller Link Units with unit version 1.2 or later
can be connected to a single CPU Unit. When connecting multiple Controller
Link Units to the CPU Unit, consider the current consumption of the CPU Unit
and each CPU Bus Unit before selecting the Power Supply Unit. For details on
Controller Link Unit current consumption, refer to
Controller Link Unit Models
and PLCs on page 16
. For details on current consumption of each Unit, refer
to the SYSMAC CJ Series Programmable Controllers Operation Manual
(W393).
The following table provides an example of current consumption
P
S
C
P
U
I
C
P
S
I
I
P
S
I
I
P
S
I
I
Of these slots, installation
is possible in up to 8 slots
(unit Ver. 1.2 or later).
Installation in up to 4 slots
is possible for pre-Ver. 1.2
Units.
CPU Rack
CJ-series Expansion
Rack
10 Unit max.
End Cover
CJ-series Expansion
Rack
10 Unit max.
End Cover
CJ-series Expansion
Rack
10 Unit max.
End Cover
10 Unit max.
End Cover
PS: Power Supply Unit
CPU: CPU Unit
IC: I/O Control Unit
II: I/O Interface Unit