Omron CS1W-RPT01 Network Card User Manual


 
91
CJ-series Controller Link Units Section 4-2
5. The default setting is “0.”
6. The unit number determines the words used by the Controller Link Unit in
PLC memory.
4-2-3 Node Addresses
Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
Note 1. When all of the following conditions are satisfied, node addresses can be
set between 01 and 62, and the network can contain up to 62 nodes.
a) All nodes in the Controller Link network use CS1W-CLK21-V1 or
CJ1W-CLK21-V1 Units.
b) The Wired Network 62 Node Enable Bit in the DM Parameter Area
software switches (bit 11 of D30000 + 100
× Unit No.) of all nodes is
turned ON.
c) At least one CS1W-RPT01 Repeater Unit is connected and the num-
ber of nodes in a single segment does not exceed 31.
2. Always turn OFF the PLC’s power before setting the node addresses.
3. Do not set the same node address twice within the same Network. An error
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light (Communications Error Flag) and ei-
ther communications will stop, or the INS indicator will not light and you will
be unable to participate in the Network.
4. When CS1W-CLK21-V1 and CJ1W-CLK21-V1 Units are used with other
models in the same Network, set the node addresses of all nodes between
1 and 32. In a network containing pre-version-1 models, it is not possible
to construct a network that uses a node address higher than 32.
Turn ON the Wired Network 62 Node Enable Bit (bit 11 of D30000 + 100
×
Unit No.) in the DM Parameter Area software switch of all CS1W-CLK21-
V1 and CJ1W-CLK21-V1 Units to restrict the network to 32 nodes maxi-
mum. If a different value is specified, the network will be incorrectly config-
ured.
5. To construct a network that uses a node address higher than 32, it is nec-
essary for all nodes to be CS1W-CLK21-V1 or CJ1W-CLK21-V1 Units.
In addition, the Wired Network 62 Node Enable Bit of the DM Parameter
Area software switch of all nodes must be turned ON to enable 62 nodes
maximum. If a different value is specified, the network will not be correctly
configured.
Item Specifications
Setting method 2-digit decimal
Setting range 01 to 32 (default is 01) (See note 1.)
Node All nodes in the Network
NODE
No.
x10
1
x10
0
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Note: The factory default settings are shown.