316
Error Log Section 9-3
0101
Hex
Transmission failed; local node
not in Network
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Refer to page 276
Troubleshooting
Using Indicators and
place the local node
into Network.
No All
0103
Hex
Transmission failed; retry count
exceeded
Using the Controller
Link Support Soft-
ware or FINS
commands, run
echoback test and
check operating envi-
ronment if errors
occur.
No All
0104
Hex
Transmission failed; maximum
number of frames exceeded.
Reduce the number
of events per com-
munications cycle or
increase the maxi-
mum number of
network parameter
frames.
No All
0105
Hex
Transmission failed; node
address incorrect
Refer to 4-2 CJ-
series Controller Link
Unitsor 4-4 CVM1
and CV-series Con-
troller Link Units and
check node address
settings to be sure
they are within range
and unique.
No All
0106
Hex
Transmission failed; redundant
node address
Correct node
addresses so that
they are unique
within the same
Network.
No All
0107
Hex
Transmission failed; destination
node not in Network
Refer to 9-1 Trouble-
shooting Using Indi-
cators and place
destination node into
Network.
No All
0108
Hex
Transmission failed; specified
Unit does not exist
Refer to 4-4 CVM1
and CV-series Con-
troller Link Units and
check unit address
and unit number of
destination.
No All
Error
code
Contents Detail code Correction Written to
EEPROM
Applicable
PLC
1st byte 2nd byte