Parker Hannifin PA Series Personal Computer User Manual


 
Chapter 2: Installing the PowerStation Selecting a Location
PA PowerStation User Guide 2-5
Class I, Division 2 Guidelines
If you purchased a Class I, Division 2-compliant PowerStation, it is suitable
for use in Groups A, B, C, and D hazardous locations. You must follow
these guidelines in order to maintain a safe operating environment.
When performing field wiring, always use copper wire with 60C or
60/75C insulation and a tightening torque of 7.0lbs/in (0.79 N-m).
Substitution of components can impair suitability for Class I, Division 2.
The PA PowerStation is intended to use a branch circuit protection rated
20 Amps or less.
Make sure that the PA PowerStation’s “ON/OFF” switch is secured in the
“ON” position using the supplied bracket.
WARNING!
Explosion Hazard!
Do not connect or disconnect cables unless the power has been
switched off, or the area is known to be non-hazardous. Keyboard,
mouse, and USB ports are for system setup and diagnostics only and
are not intended for permanent connection.
Class I, Division 2 approval requires nonincendive field wiring for
Class I, Groups A, B, C, and D hazardous locations only. With a
temperature code of T5.
Class I, Division 2 approval requires power switch restraints in
hazardous environments.