The enclosure’s surface area, A is calculated depending on the mounting or
installation type as follows:
The following table is used to calculate the recommended enclosure size for
mounting the XPSMF2DO801:
Case installation
Calculation of A [m
2
] (1m
2
=10.76ft
2
)
Single case free on all sides A = 1.8 x H x (W + D) + 1.4 x W x D
Single case for wall mounting A = 1.4 x W x (H + D) + 1.8 x H x D
End case free-standing A = 1.4 x D x (W + H) + 1.8 x W x H
End case for wall mounting A = 1.4 x H x (W + D) + 1.4 x W x D
Center case free-standing A = 1.8 x W x H + 1.4 x W x D + H x D
Center case for wall mounting A = 1.4 x W x (H + D) + H x D
Center case for wall mounting, top
surface covered
A = 1.4 x W x H + 0.7 x W x D + H x D
A the enclosure’s surface area
W width
H height
D depth