Schneider Electric XPSMF2DO801 Network Hardware User Manual


 
Equipment Description
52
33003405 07/2007
Operation
Parameters of
the Ethernet
Interfaces
Up to COM OS version 8.32 all Ethernet ports of the integrated Ethernet switches
have the same settings:
l Autoneg/Autoneg for Speed Mode
l Flow-control Mode
Other settings are not possible and will be rejected by the PLC when loading a
configuration.
The Ethernet interfaces 10/100 BaseT of the device have the following parameters:
Other devices combined with the Safety PLC or remote I/O device must have the
following network settings:
For COM OS version > 8.32 and XPSMFWIN Hardware Management version
> 7.56.10 each Ethernet port of the integrated switch can be individually configured.
See also in the appendix Connection Diagrams, Examples of Application, and Error
Codes, p. 67.
Firm operating parameters
Speed Mode Autoneg
Flow-Control Mode Autoneg
Admissible settings of other devices
Speed Mode Autoneg
Flow-Control Mode Autoneg
or
Speed Mode Autoneg
Flow-Control Mode Half Duplex
or
Speed Mode 10 or 100 Mbit/s
Flow-Control Mode Half Duplex
Non-admissible settings of other devices
Speed Mode Autoneg or 10 or 100 Mbit/s
Flow-Control Mode Full Duplex