Error Codes
Description of
Error Codes
The error codes listed in this section appear in XPSMFWIN programming
environment.
The following table describes error codes of relay outputs:
System signal R/W Meaning
Module.SRS [
UDINT] R slot number (System-Rack-Slot)
Module.Type [
UINT] R type of module, setpoint: 0x003C [60
dez
]
Module.Error Code [
WORD] R error codes of the module
0x0000
0x0001
0x0002
0x0004
0x0010
0x0020
0x0040
0x0080
I/O processing, may be faulty, see further error codes
no I/O processing (CPU not in RUN)
no I/O processing during start-up tests
manufacturer interface in operation
no I/O processing: incorrect configuration
no I/O processing: error rate exceeded
no I/O processing: configured module not inserted
DO.Error Code [
WORD] R error codes of all digital outputs
0x0001
0x0002
0x0004
0x0008
0x0010
0x0020
0x0040
0x0080
0x0100
0x0400
0x0800
0x1000
0x2000
0x4000
module error
MEZ test, safety switch 1 failed
MEZ test, safety switch 2 failed
FTZ test of test pattern failed
MEZ test of readback channels failed
MEZ test, active disconnection failed
error with initialization: relays
FTZ test: error of relay voltage
FTZ test of CS (chip select) signals failed
FTZ test: 1. temperature threshold exceeded
FTZ test: 2. temperature threshold exceeded
MEZ test: status of safety switch 1
MEZ test: status of safety switches
MEZ test: active disconection by watchdog failed