The output contacts are connected in pairs via terminal connectors, the terminals
are numbered. The terminal pins on the front plate of the module have the same
numbering sequence in order to prevent confusing connections.The terminal
connections meet the protection requirements according to IP 20. For higher
requirements the module must be enclosed in a housing with a suitable degree of
protection. The clearance and creepage distances are designed for overvoltage
category II up to 300 V according to IEC 61131-2.For the connection of voltages
besides SELV and PELV suitable cables must be used with double or reinforced
insulation (e.g. mains cable).